Top Document: Electrical Wiring FAQ (Part 1 of 2) Previous Document: Why is one prong wider than the other? Polarization Next Document: Surges, spikes, zaps, grounding and your electronics See reader questions & answers on this topic! - Help others by sharing your knowledge Older homes frequently have two-prong receptacles instead of the more modern three. These receptacles have no safety ground, and the cabling usually has no ground wire. Neither the NEC or CEC permits installing new 2 prong receptacles anymore. There are several different approaches to solving this: 1) If the wiring is done through conduit or BX, and the conduit is continuous back to the panel, you can connect the third prong of a new receptacle to the receptacle box. NEC mainly - CEC frowns on this practice. 2) If there is a metallic cold water pipe going nearby, and it's electrically continuous to the main house ground point, you can run a conductor to it from the third prong. You MUST NOT assume that the pipe is continuous, unless you can visually check the entire length and/or test it. Testing grounds is tricky - see "Testing Grounds" section. 3) Run a ground conductor back to the main panel. 4) Easiest: install a GFCI receptacle. The ground lug should not be connected to anything, but the GFCI protection itself will serve instead. The GFCI will also protect downstream (possibly also two prong outlets). If you do this to protect downstream outlets, the grounds must not be connected together. Since it wouldn't be connected to a real ground, a wiring fault could energize the cases of 3 prong devices connected to other outlets. Be sure, though, that there aren't indirect ground plug connections, such as via the sheath on BX cable. The CEC permits you to replace a two prong receptacle with a three prong if you fill the U ground with a non-conducting goop. Like caulking compound. This is not permitted in the NEC. The NEC requires that three prong receptacles without ground that are protected by GFCI must be labelled as such. See the next section about computers on GFCI-protected groundless outlets. User Contributions:Comment about this article, ask questions, or add new information about this topic:Top Document: Electrical Wiring FAQ (Part 1 of 2) Previous Document: Why is one prong wider than the other? Polarization Next Document: Surges, spikes, zaps, grounding and your electronics Part1 - Part2 - Single Page [ Usenet FAQs | Web FAQs | Documents | RFC Index ] Send corrections/additions to the FAQ Maintainer: clewis@ferret.ocunix.on.ca (Chris Lewis)
Last Update March 27 2014 @ 02:11 PM
|
I bought a new receptacle and installed the same. I still have no power I suspect there could be a bigger problem,this is aluminum wiring.
I've killed the breaker and call an electrician but am curious as to what happened.P.s. there is a dimmer switch on the same circuit.
I have multiple switches to lights. Ran 12/2 and 14/3 into switch box and inspector wrote correction needed.
What should I have done instead?
thank you
dennis
Ex: 15 amp-14awg. 12awg-20amp only rule for thumb other factors such as continuous load,heating and others if you do not know the safe NEC rules then please call a qualified journeyman Electrician better be safe